Parameter Group
-303-
Default: Model dependent Change: Unchangeable
Value Range:
-
Description
This parameter shows the fault subcode of the first fault.
F9-47
Fault protection action selection 0
Address:
63791
Min.:
0
Unit:
-
Max.: 55555 Data type: UInt16
Default:
500
Change:
At stop
Value Range:
Ones: Overcurrent during acceleration/deceleration/operation at constant speed (E2/E3/E4)
0: Coast to stop
2: Restart upon fault
Tens: Overvoltage during acceleration/deceleration or at constant speed (E5/E6/E7)
0: Coast to stop
2: Restart upon fault
Hundreds: Reserved
5: Disabled
Thousands: Undervoltage (E9)
0: Coast to stop
2: Restart upon fault
Ten thousands: AC drive overload (E10)
0: Coast to stop
2: Restart upon fault
Description
The fault protection actions are set by the ones, tens, hundreds, thousands, and ten thousands places
of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
2: Restart upon fault
The AC drive will restart upon faults.
4: Warning
The AC drive continues to run.
5: Disabled
Fault detection is disabled.
F9-48
Fault protection action selection 1
Address:
63792
Min.:
0
Unit:
-
Max.: 55555 Data type: UInt16
Default:
10050
Change:
At stop
Value Range: