Parameter Group
-304-
Ones: Motor overload (E11)
0: Coast to stop
1: Decelerate to stop
2: Restart upon fault
4: Warning
5: Disabled
Tens: Reserved
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
Hundreds: Output phase loss (E13)
0: Coast to stop
1: Decelerate to stop
2: Reset upon fault
4: Warning
5: Disabled
Thousands: IGBT overtemperature (E14)
0: Coast to stop
Ten thousands: External device fault (E15)
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
Description
The fault protection actions are set by the ones, tens, hundreds, thousands, and ten thousands places
of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
2: Restart upon fault
The AC drive will restart upon faults.
4: Warning
The AC drive continues to run.
5: Disabled
Fault detection is disabled.
F9-49
Fault protection action selection 2
Address:
63793
Min.:
0
Unit:
-
Max.: 55555 Data type: UInt16
Default:
50050
Change:
At stop
Value Range: