Parameter Group
-305-
Ones: Communication fault (E16)
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
Tens: Reserved
5: Disabled
Hundreds: Reserved
0: Coast to stop
Thousands: Motor auto-tuning fault (E19)
0: Coast to stop
4: Warning
5: Disabled
Ten thousands: Reserved
5: Disabled
Description
The fault protection actions are set by the ones, tens, hundreds, thousands, and ten thousands places
of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
4: Warning
The AC drive continues to run.
5: Disabled
Fault detection is disabled.
F9-50
Fault protection action selection 3
Address:
63794
Min.:
0
Unit:
-
Max.: 55555 Data type: UInt16
Default:
25000
Change:
At stop
Value Range:
Ones: EEPROM read-write fault
(E21)
0: Coast to stop
Tens: Motor auto-tuning result alarm
(E22)
0: Coast to stop
Hundreds: Short circuit to ground (E23)
0: Coast to stop
5: Disabled
Thousands: Reserved
5: Disabled
Ten thousands: Power supply unit fault (E25)
2: Special action
5: Disabled
Description