Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
F9-76 63820
Power dip ride-through
integral
0 to 100 30 - At once
“
F9-76
”
on page
313
F9-77 63821
Deceleration time of
power dip ride-through
0.0s to 300.0s 20.0 s At once
“
F9-77
”
on page
313
FA-00 64000
PID reference source
0: Digital setting of PID (FA-01)
1: AI1
2: AI2
3: AI3
4: Reserved
5: Communication
6: Multi-reference
0 - At once
“
FA-00
”
on page
314
FA-01 64001
Digital setting of PID
0.0% to 100.0% 50.0 % At once
“
FA-01
”
on page
314
FA-02 64002
PID feedback source
0: AI1
1: AI2
2: AI3
3: AI1 to AI2
4: Reserved
5: Communication
6: AI1 + AI2
7: Max. (|AI1|, |AI2|)
8: Min. (|AI1|, |AI2|)
0 - At once
“
FA-02
”
on page
315
FA-03 64003
PID action direction
0: Forward
1: Reverse
0 - At once
“
FA-03
”
on page
315
FA-04 64004
PID reference and
feedback range
0 to 65535 1000 - At once
“
FA-04
”
on page
315
FA-05 64005
Proportional gain Kp1
0.0 to 1000 20.0 - At once
“
FA-05
”
on page
316
FA-06 64006
Integral time Ti1
0.01s to 100.00s 2.00 s At once
“
FA-06
”
on page
316
FA-07 64007
Derivative time Td1
0.000s to 10.000s 0.000 s At once
“
FA-07
”
on page
316
FA-08 64008
PID cut-off frequency in
reverse direction
0.00 Hz to 655.35 Hz 2.00 Hz At once
“
FA-08
”
on page
316
FA-09 64009
PID deviation limit
0.0% to 100.0% 0.0 % At once
“
FA-09
”
on page
317
List of Drive Unit Parameters
-176-