Parameter Group
-216-
1: AI1
The frequency upper limit is input with current or voltage signals through the AI1 terminal. The
frequency is calculated according to the preset AI curve.
2: AI2
The frequency upper limit is input with current or voltage signals through the AI2 terminal. The
frequency is calculated according to the preset AI curve.
3: AI3
The frequency upper limit is input with current or voltage signals through the AI3 terminal. The
frequency is calculated according to the preset AI curve.
5: Communication
The frequency upper limit is set through communication.
6: Multi-speed reference
The frequency upper limit is determined by the multi-speed references set in FC-00 to FC-15.
F0-12
Frequency upper limit
Address:
61452
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
50.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
This parameter defines the maximum running frequency allowed for the motor.
F0-13
Frequency upper limit offset
Address:
61453
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
0.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
This parameter defines the offset of the frequency upper limit. It is used to adjust the output
frequency value upon minimum frequency reference signal when the frequency is set by an external
analog signal (voltage or current).
F0-14
Frequency lower limit
Address:
61454
Min.:
0.00
Unit:
Hz
Max.: 655.35 Data type: UInt16
Default:
0.00
Change:
At once
Value Range:
0.00 Hz to 655.35 Hz
Description
This parameter defines the minimum running frequency for the motor.
F0-15
Carrier frequency
Address:
61455
Min.:
0.8
Unit:
kHz
Max.: 15.0 Data type: UInt16
Default: Model dependent Change:
At once