Parameter Group
-223-
F1-10
Asynchronous motor no-load current
Address:
61706
Min.:
0.1
Unit:
A
Max.: 6553.5 Data type: UInt16
Default: Model dependent Change:
At stop
Value Range:
0.1 A to 6553.5 A
Description
This parameter defines the current passing through the three-phase winding of the stator when the
motor is running without load. It can be obtained by dynamic auto-tuning of the motor.
F1-11
Asynchronous motor core saturation coefficient 1
Address:
61707
Min.:
50.0
Unit:
%
Max.: 100.0 Data type: UInt16
Default:
86.0
Change:
At once
Value Range:
50.0% to 100.0%
Description
This parameter defines core saturation coefficient 1 of the asynchronous motor.
F1-12
Asynchronous motor core saturation coefficient 2
Address:
61708
Min.:
100.0
Unit:
%
Max.: 150.0 Data type: UInt16
Default:
130.0
Change:
At once
Value Range:
100.0% to 150.0%
Description
This parameter defines core saturation coefficient 2 of the asynchronous motor.
F1-13
Asynchronous motor core saturation coefficient 3
Address:
61709
Min.:
100.0
Unit:
%
Max.:
170.0
Data type:
UInt16
Default:
140.0
Change:
At once
Value Range:
100.0% to 170.0%
Description
This parameter defines core saturation coefficient 3 of the asynchronous motor.
F1-14
Asynchronous motor core saturation coefficient 4
Address:
61710
Min.:
100.0
Unit:
%
Max.: 180.0 Data type: UInt16
Default:
150.0
Change:
At once
Value Range:
100.0% to 180.0%
Description
This parameter defines core saturation coefficient 4 of the asynchronous motor.
F1-17
Synchronous motor axis D inductance
Address:
61713