Parameter Group
-252-
0: Two-wire mode 1
Two DI terminals are connected: one is used to start/stop the AC drive in forward run mode, and the
other is used to start/stop the AC drive in reverse run mode.
1: Two-wire mode 2
Two DI terminals are connected: one is used to start/stop the AC drive, and the other is used to
control the running direction.
2: Three-wire mode 1
Three DI terminals are connected: one is used to start/stop the AC drive, and the other two are used
to control the running direction.
3: Three-wire mode 2
Three DI terminals are connected: one is used to start the AC drive, one is used to stop the AC drive,
and the other is used to control the running direction.
F4-18
Terminal UP/DOWN change rate
Address:
62482
Min.:
001
Unit:
Hz/s
Max.: 65.535 Data type: UInt16
Default:
1.000
Change:
At once
Value Range:
0.001 Hz/s to 65.535 Hz/s
Description
This parameter defines the change rate when the frequency is adjusted through terminal UP/DOWN.
It must be set when the function of a DI terminal is set to terminal UP or terminal DOWN (any one of
F4-01 to F4-15 is set to 6 or 7).
F4-19
DI1 delay
Address:
62483
Min.:
0.0
Unit:
s
Max.:
3600.0
Data type: UInt16
Default:
0.0
Change:
At once
Value Range:
0.0s to 3600.0s
Description
This parameter defines the delay of the DI state change. The delay setting function is available only
for DI1, DI2, and DI3 currently.
F4-20
DI2 delay
Address:
62484
Min.:
0.0
Unit:
s
Max.:
3600.0
Data type: UInt16
Default:
0.0
Change:
At once
Value Range:
0.0s to 3600.0s
Description
This parameter defines the delay of the DI state change. The delay setting function is available only
for DI1, DI2, and DI3 currently.
F4-21
DI3 delay
Address:
62485
Min.:
0.0
Unit:
s
Max.:
3600.0
Data type: UInt16