Parameter Group
-253-
Default:
0.0
Change:
At once
Value Range:
0.0s to 3600.0s
Description
This parameter defines the delay of the DI state change. The delay setting function is available only
for DI1, DI2, and DI3 currently.
F4-22
DI active mode setting 1
Address:
62486
Min.:
0
Unit:
-
Max.: 11111 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
Ones:
0: Active high
1: Active low
Tens:
0: Active high
1: Active low
Hundreds:
0: Active high
1: Active low
Thousands:
0: Active high
1: Active low
Ten thousands:
0: Active high
1: Active low
Description
The active mode for terminals DI1 to DI5 are set by ones, tens, hundreds, thousands, and ten
thousands of this parameter.
0: Active high
The DI terminals (DI1 to DI5) are active when connected to COM and inactive when disconnected from
COM.
1: Active low
The DI terminals (DI1 to DI5) are inactive when connected to COM and active when disconnected from
COM.
F4-23
DI active mode setting 2
Address:
62487
Min.:
0
Unit:
-
Max.: 11111 Data type: UInt16
Default:
0
Change:
At stop
Value Range: