Parameter Group
-254-
Ones:
0: Active high
1: Active low
Tens:
0: Active high
1: Active low
Hundreds:
0: Active high
1: Active low
Thousands:
0: Reserved
Ten thousands:
0: Reserved
Description
The active mode for terminals DI1 to DI8 are set by ones, tens, hundreds, thousands, and ten
thousands of this parameter.
0: Active high
The DI terminals (DI6 to DI8) are active when connected to COM and inactive when disconnected from
COM.
1: Active low
The DI terminals (DI6 to DI8) are inactive when connected to COM and active when disconnected from
COM.
F4-25
AI1 hardware source
Address:
62489
Min.:
0
Unit:
-
Max.: 208 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Not selected
1: AI1 of power supply unit
2: AI2 of power supply unit
101: AI1 of extension card 1
102: AI2 of extension card 1
201: AI1 of extension card 2
202: AI2 of extension card 2
Description
This parameter defines the analog/temperature input source.
F4-27
AI2 hardware source
Address:
62491
Min.:
0
Unit:
-
Max.: 202 Data type: UInt16
Default:
0
Change:
At stop
Value Range: