Parameter Group
-275-
3: Forward jog
The MF.K key is used for enabling forward jog (FJOG). This function is valid only when the command
source is set to operating panel control.
4: Reverse jog
The MF.K key is used for enabling reverse jog (RJOG). This function is available only when the
command source is set to the operating panel.
F7-02
STOP key function
Address:
63234
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: STOP key enabled only in operating panel control mode
1: STOP key enabled in any operating mode
Description
The STOP key on the operating panel is used for stop/reset. This parameter is used to set the function
of this key.
0: STOP key enabled only in operating panel control mode
The STOP key is valid only in operating panel control mode.
1: STOP key enabled in any operating mode
The STOP key is valid in any operating mode.
F7-03
LED display 1 in running state
Address:
63235
Min.:
0
Unit:
-
Max.: 0 Data type: UInt16
Default:
31
Change:
At once
Value Range:
Bit00: Running frequency (Hz)
Bit01: Frequency reference (Hz)
Bit02: Bus voltage (V)
Bit03: Output voltage (V)
Bit04: Output current (A)
Bit05: Output power (kW)
Bit06: Output torque (%)
Bit07: DI status
Bit08: DO status
Bit09: AI1 voltage (V)
Bit10: AI2 voltage (V)
Bit11: AI3 voltage (V)
Bit12: Count value
Bit13: Length value
Bit14: Load speed display
Bit15: PID reference
Description
To display a parameter during running, set the corresponding bit to 1, convert the binary number to a
hexadecimal equivalent, and set it in F7-03.