Parameter Group
-295-
F9-06
Output phase loss detection before startup
Address:
63750
Min.:
0
Unit:
%
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Disabled
1: Enabled
Description
It takes about several seconds to detect output phase loss during running. For low-frequency running
applications or applications where risks exist in start with phase loss, this function enables quick
detection of output phase loss during startup. However, it does not apply to applications that have
strict requirements on startup time.
F9-07
Detection of short-circuit to ground
Address:
63751
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
1
Change:
At stop
Value Range:
0: Not detection
1: Detection before power-on
Description
This parameter defines whether to enable or disable the short-circuit to ground detection function.
F9-09 Auto reset attempts
Address:
63753
Min.:
0
Unit:
-
Max.: 20 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0 to 20
Description
This parameter defines the number of auto fault reset attempts of the AC drive. If the number of reset
attempts exceeds the value of this parameter, the AC drive will remain in the faulty state.
F9-10
DO action during auto fault reset
Address:
63754
Min.:
0
Unit:
-
Max.: 1 Data type:
UInt16
Default:
0
Change:
At once
Value Range:
0: Not act
1: Act
Description
This parameter defines whether the faulty DO (assigned with function 3) acts during auto fault reset if
the auto fault reset function is enabled.
F9-11
Auto reset interval
Address:
63755
Min.:
0.1
Unit:
s
Max.: 100.0 Data type: UInt16