Parameter Group
-296-
Default:
1.0
Change:
At once
Value Range:
0.1s to 100.0s
Description
This parameter defines the delay of auto fault reset after the AC drive reports a fault.
F9-12
Restart interval upon fault reset
Address:
63755
Min.:
0
Unit:
s
Max.:
100.0
Data type:
UInt16
Default:
1.0
Change:
At once
Value Range:
0s to 100.0s
Description
This parameter defines the delay of restart after automatic fault reset of the AC drive.
F9-13
STO safety state reset mode
Address:
63757
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Manual
1: Auto
Description
This parameter defines whether auto reset is performed after the system triggers STO and then
recovers.
0: Manual
After the system triggers STO and then recovers, manual reset is required.
1: Auto
After the system triggers STO and then recovers, auto reset is performed.
F9-14
1st fault type
Address:
63758
Min.:
0
Unit:
-
Max.: 99 Data type: UInt16
Default: Model dependent Change: Unchangeable
Value Range:
0 to 99
Description
This parameter shows the fault codes of the latest three (1st, 2nd, and 3rd (latest)) faults. The host
controller reads the communication address to obtain the fault code of the AC drive and triggers the
AC drive to report the fault. The fault code can be viewed on the operating panel.
F9-15
2nd fault type
Address:
63759
Min.:
0
Unit:
-
Max.: 99 Data type: UInt16
Default: Model dependent Change: Unchangeable
Value Range:
0 to 99

Table of Contents