Parameter Group
-310-
Min.:
0
Unit: °C
Max.: 200 Data type: UInt16
Default:
90
Change:
At once
Value Range:
0°C to 200°C
Description
Motor overheat pre-warning threshold 2 When the motor temperature measured by the sensor
connected to the hardware source mapped to AI2 exceeds the value of F9-60 (motor overheat pre-
warning threshold) and the function of the DO/RO terminal is set to 9 (motor overtemperature), the
DO/RO terminal outputs an active signal.
F9-61
Motor overheat protection threshold 3
Address:
63805
Min.:
0
Unit: °C
Max.: 200 Data type: UInt16
Default:
110
Change:
At once
Value Range:
0°C to 200°C
Description
Motor overheat protection threshold 3 When the motor temperature measured by the sensor
connected to the hardware source mapped to AI3 exceeds the value of F9-61 (motor overheat
protection threshold 1), the AC drive reports a motor overtemperature fault (E45.00) and acts
according to F9-53 (fault protection action selection 6).
F9-62
Motor overheat pre-warning threshold 3
Address:
63806
Min.:
0
Unit: °C
Max.: 200 Data type: UInt16
Default:
90
Change:
At once
Value Range:
0°C to 200°C
Description
Motor overheat pre-warning threshold 3 When the motor temperature measured by the sensor
connected to the hardware source mapped to AI3 exceeds the value of F9-62 (motor overheat pre-
warning threshold) and the function of the DO/RO terminal is set to 9 (motor overtemperature), the
DO/RO terminal outputs an active signal.
F9-63
Power dip ride-through function selection
Address:
63807
Min.:
0
Unit:
-
Max.: 2 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Disabled
1: Decelerate
2: Decelerate to stop
Description