Parameter Group
-309-
Max.: 100.0 Data type: UInt16
Default:
100.0
Change:
At once
Value Range:
0.0% to 100.0%
Description
This parameter defines the alternative frequency of the AC drive upon fault. If a fault occurs during
running and the fault protection action is to run at the alternative frequency upon error (F9-54 = 4),
the AC drive displays A** and continues running at the alternative frequency.
F9-57
Motor overheat protection threshold 1
Address:
63801
Min.:
0
Unit: °C
Max.: 200 Data type: UInt16
Default:
110
Change:
At once
Value Range:
0°C to 200°C
Description
Motor overheat protection threshold 1 When the motor temperature measured by the sensor
connected to the hardware source mapped to AI1 exceeds the value of F9-57 (motor overheat
protection threshold 1), the AC drive reports a motor overtemperature fault (E45.00) and acts
according to F9-53 (fault protection action selection 6).
F9-58
Motor overheat pre-warning threshold 1
Address:
63802
Min.:
0
Unit: °C
Max.: 200 Data type: UInt16
Default:
90
Change:
At once
Value Range:
0°C to 200°C
Description
Motor overheat pre-warning threshold 1 When the motor temperature measured by the sensor
connected to the hardware source mapped to AI1 exceeds the value of F9-58 (motor overheat pre-
warning threshold) and the function of the DO/RO terminal is set to 9 (motor overtemperature), the
DO/RO terminal outputs an active signal.
F9-59
Motor overheat protection threshold 2
Address:
63803
Min.:
0
Unit: °C
Max.: 200 Data type: UInt16
Default:
110
Change:
At once
Value Range:
0°C to 200°C
Description
Motor overheat protection threshold 2 When the motor temperature measured by the sensor
connected to the hardware source mapped to AI2 exceeds the value of F9-59 (motor overheat
protection threshold 2), the AC drive reports a motor overtemperature fault (E45.00) and acts
according to F9-53 (fault protection action selection 6).
F9-60
Motor overheat pre-warning threshold 2
Address:
63804