Parameter Group
-308-
Max.: 55555 Data type: UInt16
Default:
5500
Change:
At stop
Value Range:
Ones: Motor overtemperature (E45)
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
Tens: Reserved
5: Disabled
Hundreds: Reserved
5: Disabled
Thousands: Reserved
5: Disabled
Ten thousands: Fan fault (E80)
0: Coast to stop
1: Decelerate to stop
5: Disabled
Description
The fault protection actions are set by the ones, tens, hundreds, thousands, and ten thousands places
of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
4: Warning
The AC drive continues to run.
5: Disabled
Fault detection is disabled.
F9-54
Frequency selection for continuing to run upon fault
Address:
63798
Min.:
0
Unit:
-
Max.: 4 Data type: UInt16
Default:
1
Change:
At once
Value Range:
0: Current running frequency
1: Frequency reference
2: Frequency upper limit
3: Frequency lower limit
4: Alternative frequency upon exception
Description
This parameter defines the frequency at which the AC drive continues to run when it is faulty. If a fault
occurs during running of the AC drive and the fault protection action is set to "Continue to run", the
AC drive displays A** and continues to run at the frequency defined by F9-54.