Parameter Group
-357-
A6-02
Curve 4 inflection point 1 input
Address:
42498
Min.:
–10.00
Unit:
V
Max.: 10.00 Data type: Int16
Default:
3.00
Change:
At once
Value Range:
-10.00 V to 10.00 V
Description
This parameter defines the x-axis of inflection 1 on AI curve 4, that is, the analog input voltage (or
analog input current) at inflection 1.
A6-03
Percentage corresponding to curve 4 inflection point 1 input
Address:
42499
Min.:
–100.0
Unit:
%
Max.: 100.0 Data type: Int16
Default:
30.0
Change:
At once
Value Range:
–100.0% to 100.0%
Description
This parameter defines the y-axis of inflection 1 on AI curve 4, that is, the percentage of the analog
input at inflection 1 relative to the maximum frequency.
A6-04
Curve 4 inflection point 2 input
Address:
42500
Min.:
–10.00
Unit:
V
Max.:
10.00
Data type:
Int16
Default:
6.00
Change:
At once
Value Range:
-10.00 V to 10.00 V
Description
This parameter defines the x-axis of inflection 2 on AI curve 4, that is, the analog input voltage (or
analog input current) at inflection 2.
A6-05
Percentage corresponding to curve 4 inflection point 2 input
Address:
42501
Min.:
–100.0
Unit:
%
Max.: 100.0 Data type: Int16
Default:
60.0
Change:
At once
Value Range:
–100.0% to 100.0%
Description
This parameter defines the y-axis of inflection 2 on AI curve 4, that is, the percentage of the analog
input at inflection 2 relative to the maximum frequency.
A6-06
Curve 4 maximum input
Address:
42502
Min.:
–10.00
Unit:
V
Max.: 10.00 Data type: Int16
Default:
10.00
Change:
At once
Value Range:
-10.00 V to 10.00 V