Parameter Group
-358-
Description
This parameter defines the x-axis of the maximum input point on AI curve 4, that is, the maximum
analog input voltage (or maximum analog input current).
A6-07
Percentage corresponding to curve 4 maximum input
Address:
42503
Min.:
–100.0
Unit:
%
Max.: 100.0 Data type: Int16
Default:
100.0
Change:
At once
Value Range:
–100.0% to 100.0%
Description
This parameter defines the y-axis of the maximum input point on AI curve 4, that is, the percentage of
the maximum analog input relative to the maximum frequency.
A6-08
Curve 5 minimum input
Address:
42504
Min.:
–10.00
Unit:
V
Max.: 10.00 Data type: Int16
Default:
–10.00
Change:
At once
Value Range:
–10.00 V to 10.00 V
Description
This parameter defines the x-axis of the minimum input point on AI curve 5, that is, the minimum
analog input voltage (or minimum analog input current).
A6-09
Percentage corresponding to curve 5 minimum input
Address:
42505
Min.:
–100.0
Unit:
%
Max.: 100.0 Data type: Int16
Default:
–100.0
Change:
At once
Value Range:
–100.0% to 100.0%
Description
This parameter defines the y-axis of the minimum input point on AI curve 5, that is, the percentage of
the minimum analog input relative to the maximum frequency.
A6-10
Curve 5 inflection point 1 input
Address:
42506
Min.:
–10.00
Unit:
V
Max.: 10.00 Data type: Int16
Default:
–3.00
Change:
At once
Value Range:
–10.00 V to 10.00 V
Description
This parameter defines the x-axis of inflection 1 on AI curve 5, that is, the analog input voltage (or
analog input current) at inflection 1.
A6-11
Percentage corresponding to curve 5 inflection point 1 input
Address:
42507
Min.:
–100.0
Unit:
%