Parameter Group
-365-
Description
This parameter defines coefficient 2 of quick auto-tuning of stator resistance of the asynchronous
motor.
A9-15
Coefficient 3 of quick auto-tuning of asynchronous motor stator resistance
Address:
43279
Min.:
0
Unit:
-
Max.: 65535 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0 to 65535
Description
This parameter defines coefficient 3 of quick auto-tuning of stator resistance of the asynchronous
motor.
A9-17
Synchronous motor real-time angle
Address:
43281
Min.:
0
Unit:
-
Max.:
65535
Data type:
UInt16
Default:
0
Change: Unchangeable
Value Range:
0 to 65535
Description
This parameter shows the real-time angle of the synchronous motor.
A9-18
Initial angle detection of synchronous motor
Address:
43282
Min.:
0
Unit:
-
Max.: 2 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Detected upon running
1: Not detected
2: Detected upon initial running after power-on
Description
This parameter defines the detection mode of the initial position angle of the synchronous motor.
The default value is recommended.
A9-20
Field weakening mode
Address:
43284
Min.:
0
Unit:
-
Max.:
3
Data type: UInt16
Default:
1
Change:
At stop
Value Range:
0: Automatic mode
1: Synchronous motor adjustment mode
2: Synchronous motor hybrid mode
3: Disabled
Description
This parameter defines the field weakening mode. The default value is recommended.