Function Applications
-525-
Related Parameters
Parame
ter No.
Parameter Name
Default
Value
Setting Range Parameter Description
F9-47
Fault protection
action selection 0
500
Ones position: E2/E3/E4
0: Coast to stop
2: Restart upon fault
Tens position: E5/E6/E7
0: Coast to stop
2: Restart upon fault
Hundreds position:
Reserved
5: Canceled
Thousands position: E9
0: Coast to stop
2: Restart upon fault
Ten thousands position:
E10
0: Coast to stop
2: Restart upon fault
The fault protection actions are set
through the ones, tens, hundreds,
thousands, and ten thousands
positions of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
2: Restart upon fault
The AC drive will restart upon faults.
4: Alarm
The AC drive continues to run.
5: Canceled
The fault detection is disabled.
F9-48
Fault protection
action selection 1
10050
Ones position: E11
0: Coast to stop
1: Decelerate to stop
2: Restart upon fault
4: Alarm
5: Canceled
Tens position: Reserved
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
Hundreds position: E13
0: Coast to stop
1: Decelerate to stop
2: Restart upon fault
4: Alarm
5: Canceled
Thousands position: E14
0: Coast to stop
Ten thousands position:
E15
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
The fault protection actions are set
through the ones, tens, hundreds,
thousands, and ten thousands
positions of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
2: Restart upon fault
The AC drive will restart upon faults.
4: Alarm
The AC drive continues to run.
5: Canceled
The fault detection is disabled.