Function Applications
-526-
Parame
ter No.
Parameter Name
Default
Value
Setting Range Parameter Description
F9-49
Fault protection
action selection 2
00050
Ones position: E16
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
Tens position: Reserved
5: Canceled
Hundreds position:
Reserved
0: Coast to stop
Thousands position: E19
0: Coast to stop
4: Alarm
5: Canceled
Ten thousands position:
Reserved
5: Canceled
The fault protection actions are set
through the ones, tens, hundreds,
thousands, and ten thousands
positions of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
2: Restart upon fault
The AC drive will restart upon faults.
4: Alarm
The AC drive continues to run.
5: Canceled
The fault detection is disabled.
F9-50
Fault protection
action selection 3
25000
Ones position: E21
0: Coast to stop
Tens position: E22
0: Coast to stop
Hundreds position: E23
0: Coast to stop
5: Canceled
Thousands position:
Reserved
5: Canceled
Ten thousands position:
E25
2: Special action
5: Canceled
The fault protection actions are set
through the ones, tens, hundreds,
thousands, and ten thousands
positions of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
2: Special action
The AC drive will stop according to the
stop command sent by the power
supply unit.
4: Alarm
The AC drive continues to run.
5: Canceled
The fault detection is disabled.