EasyManua.ls Logo

Inovance MD800 Series - Page 528

Inovance MD800 Series
565 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function Applications
-527-
Parame
ter No.
Parameter Name
Default
Value
Setting Range Parameter Description
F9-51
Fault protection
action selection 4
51111
Ones position: E26
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
Tens position: E27
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
Hundreds position: E28
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
Thousands position: E29
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
Ten thousands position:
E30
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
The fault protection actions are set
through the ones, tens, hundreds,
thousands, and ten thousands
positions of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
4: Alarm
The AC drive continues to run.
5: Canceled
The fault detection is disabled.

Table of Contents

Other manuals for Inovance MD800 Series

Related product manuals