Function Applications
-528-
Parame
ter No.
Parameter Name
Default
Value
Setting Range Parameter Description
F9-52
Fault protection
action selection 5
00101
Ones position: E31
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
Tens position: Reserved
5: Canceled
Hundreds position:
Reserved
5: Canceled
Thousands position: E42
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
Ten thousands position:
E43
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
The fault protection actions are set
through the ones, tens, hundreds,
thousands, and ten thousands
positions of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
4: Alarm
The AC drive continues to run.
5: Canceled
The fault detection is disabled.
F9-53
Fault protection
action selection 6
05500
Ones position: E45
0: Coast to stop
1: Decelerate to stop
4: Alarm
5: Canceled
Tens position: Reserved
5: Canceled
Hundreds position:
Reserved
5: Canceled
Thousands position:
Reserved
5: Canceled
Ten thousands position:
E80
0: Coast to stop
1: Decelerate to stop
5: Canceled
The fault protection actions are set
through the ones, tens, hundreds,
thousands, and ten thousands
positions of this parameter.
0: Coast to stop
The AC drive coasts to stop.
1: Decelerate to stop
The AC drive decelerates to stop.
4: Alarm
The AC drive continues to run.
5: Canceled
The fault detection is disabled.