Function Applications
-545-
Para. No. Name
Basic Unit
Value Range Description
U0-56
Identified axis
type
1 1 to 3
Axis type identified by the AC drive
1: Single axis
2: Dual-axis 1
3: Dual-axis 2
U0-57
Reserved
- - -
U0-61
AC drive
operation
status word 1
1
-
AC drive operation status word 1
1: Forward running
2: Reverse running
3: Stop
4: Auto-tuning
5: Faulty
U0-64
Special
protocol status
word
1
-
AC drive operation status word 2
Bit1 to Bit0: Running status
Bit2: Jog enabled or not
Bit4 to Bit3: Running direction state
Bit3 to Bit7: Reserved
Bit8: Main frequency set by communication
Bit9: Main frequency set by AI
Bit10: Command source from
communication
Bit11 to Bit15: Reserved
U0-68
AC drive
operation
status word 2
1
-
AC drive operation status word 2
Bit0: Running status
Bit1: Forward/Reverse state
Bit2: Whether a fault occurs
Bit3: Whether the output frequency reaches
the frequency reference
Bit4: Communication normal flag
Bit5 to Bit7: Reserved
Bit8 to Bit15: Fault code
U0-78
AC drive rated
current
0.1 A
0.0 A to AC drive rated
current
Rated current (A) of the AC drive
U0-79
AC drive power
0.1 kW
0.0 kW to rated AC
drive power
Rated power (kW) of the AC drive
U0-81
Local LED
status
1
-
LED status of the drive unit
Bit0: RUN indicator
Bit1: Fault indicator
U0-88
Alarm code
1
-
Alarm code of the AC drive
U0-89
Alarm subcode
1
-
Alarm subcode of the AC drive
U0-90
Fan speed
percentage
reference
1%
-
Current speed reference of the fan