Parameter Group
-75-
Default:
0
Change:
At once
Value Range:
0 to 127
Description
Manual setting of drive unit 7 station number
FD-48
Manual setting of drive unit 8 station number
Address:
64816
Min.:
0
Unit:
-
Max.: 127 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0 to 127
Description
Manual setting of drive unit 8 station number
FD-50
Startup with slave mismatch
Address:
64818
Min.:
0
Unit:
-
Max.: 1 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0: Disabled
1: Enabled
Description
0: The communication error E16.74 is reported when the number of slave stations configured for the
PLC is inconsistent with the actual number of slave stations in the network.
1: No communication error is reported when the number of slave stations configured for the PLC is
inconsistent with the actual number of slave stations in the network.
FD-51
Slave station communication inhibit time
Address:
64819
Min.:
0
Unit:
ms
Max.: 65535 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
0 ms to 65535 ms
Description
This parameter specifies the slave station communication inhibit time.
FD-52
Number of online slave stations
Address:
64820
Min.:
0
Unit:
-
Max.: 30 Data type: UInt16
Default:
0
Change: Unchangeable
Value Range:
0 to 30
Description
This parameter defines the number of online slave stations.
FD-53
Online status of slave stations 1 to 15
Address:
64821