10 Parameter List
138 of
212
PumpDrive 2
Parameter Description Help text Possible settings Unit Factory setting
1-3-9-1 Alternative Setpoint
(Closed-loop Control)
Alternative configurable setpoint (can be
activated via time or DIGIN; DIGIN has
priority). This parameter is disabled if the
setpoint is specified via DIGIN/ANIN.
Otherwise, the setpoint source is selected
via the Control Point parameter (Local/Field
Bus).
Minimum to maximum limit of value range
set
Dependent on the
controlled
variable set
0,00
1-3-9-2 Alternative Control
Value (Open-Loop
Control)
Alternative configurable control value for
speed in open-loop control mode
3-2-2-1 … 3-2-2-2 rpm 500
1-3-9-3 Start of Alternative
Setpoint/Control Value
Start of toggle from setpoint/control value
to alternative setpoint/control value
00:00…23:59 h 00:00
1-3-9-4 End of Alternative
Setpoint/Control Value
End of toggle from setpoint/control value
to alternative setpoint/control value
00:00…23:59 h 00:00
1-4 Meter
1-4-1 Energy
1-4-1-1 Energy Meter (kWh) Current energy consumption of pump set kWh 0
1-4-1-2 Reset Energy Meter Resetting the pump set's kWh meter Run
1-4-1-3 Power Saved Power saved in relation to fixed speed
pump
kW 0,00
1-4-1-4 Energy Saved Energy saved in relation to fixed speed
pump
kWh 0
1-4-1-5 CO2 Emission Reduction Reduction in carbon dioxide emissions in
relation to fixed speed pump
t 0,0
1-4-1-6 Costs Saved Energy cost savings, in national currency, in
relation to fixed speed pump
0,00
1-4-1-7 Reset Energy Savings
Meter
Reset Energy Savings Meter Run
1-4-2 Operation
1-4-2-1 Frequency Inverter
Operating Hours
Operating hours of frequency inverter in
standby (sleep) mode and during operation
h 0
1-4-2-2 Reset Frequency Inverter
Operating Hours
Resetting operating hours counter of
frequency inverter
Run
1-4-2-3 Pump Operating Hours Operating hours of pump in active
operation
h 0
1-4-2-4 Reset Pump Operating
Hours
Resetting operating hours counter of pump Run