10 Parameter List
PumpDrive 2
165 of
212
Parameter Description Help text Possible settings Unit Factory setting
3-8-9-2 Time Delay ON Period of time during which the event
selected must be continually available until
the relay is set
0,0 … 10,0 s 0,5
3-8-9-3 Time Delay OFF Period of time for which the event selected
must have gone before the relay is reset
0,0 … 10,0 s 0,5
3-8-10 Relay Output 2
3-8-10-1 Relay 2 Function Selectable messages via relay 2 ▪ No function
▪ AUTO operating mode
▪ RUN operating status
▪ AUTO/SLEEP operating status
▪ Warning
▪ Alert
▪ Alert or Warning
▪ No alert
▪ Dynamic overload protection
▪ Current too high
▪ Current too low
▪ Frequency too high
▪ Frequency too low
▪ Power too high
▪ Power too low
▪ Actual value = setpoint
RUN operating
status
3-8-10-2 Time Delay ON Period of time during which the event
selected must be continually available until
the relay is set
0,0 … 10,0 s 0,5
3-8-10-3 Time Delay OFF Period of time for which the event selected
must have gone before the relay is reset
0,0 … 10,0 s 0,5
3-8-11 Relay Output 3 Selectable messages via relay 3 of I/O
extension board