10 Parameter List
PumpDrive 2
173 of
212
Parameter Description Help text Possible settings Unit Factory setting
3-8-18-1 Digital Output 2
Function
Selectable messages via digital output 2 of I/
O extension board
▪ No function
▪ AUTO operating mode
▪ RUN operating status
▪ AUTO/SLEEP operating status
▪ Warning
▪ Alert
▪ Alert or Warning
▪ No alert
▪ Dynamic overload protection
▪ Current too high
▪ Current too low
▪ Frequency too high
▪ Frequency too low
▪ Power too high
▪ Power too low
▪ Actual value = setpoint
No function
3-8-18-2 Time Delay ON Period of time during which the event
selected must be continually available until
the digital output is set
0,0 … 600,0 s 0,5
3-8-18-3 Time Delay OFF Period of time for which the event selected
must have gone before the digital output is
reset
0,0 … 600,0 s 0,5
3-8-18-3 Time Delay OFF Period of time for which the event selected
must have gone before the digital output is
reset
0,0 … 600,0 s 0,5
3-9 Application Functions
3-9-1 Broken Wire Detection
3-9-1-1 Response to Failure Frequency inverter response to No Master
Control alert
▪ All Pumps OFF
▪ Fixed Speed
All Pumps OFF