10 Parameter List
178 of
212
PumpDrive 2
Parameter Description Help text Possible settings Unit Factory setting
3-9-12-1 Lower Limit Lower speed limit for suppressing the
resonance range. If the lower and upper
limit frequency are assigned the same
values, there is no suppression. This
function is not supported in manual mode.
3-2-2-1 … 3-2-2-2 rpm 3-2-2-1
3-9-12-2 Upper Limit Upper speed limit for suppressing the
resonance range. If the lower and upper
limit frequency are assigned the same
values, there is no suppression. This
function is not supported in manual mode.
3-2-2-1 … 3-2-2-2 rpm 3-2-2-1
3-9-13 Service Interval
3-9-13-1 Interval Time Time interval between notifications for
upcoming maintenance service
0 … 48 Months 0
3-9-13-2 Reset Service Interval Resetting the service interval Run
3-9-14 External Message
3-9-14-1 Response to External
Message
Response to output of external message Alert
Warning
Alert
3-9-14-2 Behaviour of External
Message
Alarm behaviour of external message Self-acknowledging
Non-self-acknowledging
Non-self-
acknowledging
3-10 Monitoring Functions
3-10-1 Power
3-10-1-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
3-11-6-1 … 3-10-1-2 Dependent on the
unit set
0,00
3-10-1-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-1-1 … 3-11-6-2 Dependent on the
unit set
500,00
3-10-1-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s 3,0
3-10-2 Current
3-10-2-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
3-11-7-1 … 3-10-2-2 A 0,00