10 Parameter List
PumpDrive 2
179 of
212
Parameter Description Help text Possible settings Unit Factory setting
3-10-2-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-2-1 … 3-11-7-2 A 150,00
3-10-2-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s 3,0
3-10-3 Speed
3-10-3-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
3-11-1-1 … 3-10-3-2 rpm 3-2-2-1
3-10-3-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-3-1 … 3-11-1-2 rpm 3-11-1-2
3-10-3-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s 3,0
3-10-4 Setpoint
3-10-4-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
Minimum limit of value range set up to
3-10-4-2
Dependent on the
unit set
3-10-4-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-4-1 up to maximum limit of value
range set
Dependent on the
unit set
3-10-4-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s 3,0
3-10-5 Actual Value
3-10-5-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
Minimum limit of value range set up to
3-10-5-2
Dependent on the
unit set
3-10-5-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-5-1 up to maximum limit of value
range set
Dependent on the
unit set