10 Parameter List
180 of
212
PumpDrive 2
Parameter Description Help text Possible settings Unit Factory setting
3-10-5-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s 3,0
3-10-6 Flow rate
3-10-6-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
3-11-3-1 … 3-10-6-2 Dependent on the
unit set
Application-
specific
3-10-6-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-6-1 … 3-11-3-2 Dependent on the
unit set
Application-
specific
3-10-6-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s 3,0
3-10-7 Suction pressure
3-10-7-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
3-11-2-1 … 3-10-7-2 Dependent on the
unit set
3-10-7-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-7-1 … 3-11-2-2 Dependent on the
unit set
3-10-7-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s
3-10-8 Discharge pressure
3-10-8-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
3-11-2-1 … 3-10-8-2 Dependent on the
unit set
3-10-8-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-8-1 … 3-11-2-2 Dependent on the
unit set
3-10-8-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s 3,0