10 Parameter List
PumpDrive 2
181 of
212
Parameter Description Help text Possible settings Unit Factory setting
3-10-9 Differential Pressure
3-10-9-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
3-11-2-1 … 3-10-9-2 Dependent on the
unit set
3-10-9-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-9-1 … 3-11-2-2 Dependent on the
unit set
3-10-9-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s 3,0
3-10-10 Frequency
3-10-10-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
3-11-8-1 … 3-10-10-2 Hz 0,00
3-10-10-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-10-1 … 3-11-8-2 Hz 70,00
3-10-10-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s 3,0
3-10-11 Temperature
3-10-11-1 Lower Limit Defining the lower limit value for warning.
When the lower limit value is undershot, a
warning is triggered after the time delay
has lapsed.
3-11-4-1 … 3-10-11-2 Dependent on the
unit set
3-10-11-2 Upper Limit Defining the upper limit value for warning.
When the upper limit value is exceeded, a
warning is triggered after the time delay
has lapsed.
3-10-11-1 … 3-11-4-2 Dependent on the
unit set
3-10-11-3 Time Delay Period of time for which the limit value
must be continually violated before a
warning is triggered
0,0 … 600,0 s 3,0
3-11 Value Ranges and Units
3-11-1 Speed
3-11-1-1 Minimum Speed Minimum limit of measuring range 0 … 4200 rpm 0