EDS94ARNExxxx EN 2.3 - 06/2014 L 283
9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00143
C00143
C00144
C00145
Parameter | Name:
C00143 | Sampled peak power
Data type: UNSIGNED_32
Index: 24432
d
= 5F70
h
From software version V2.0 onwards
C00144/1...3
display the elapsed-hour meter reading at which the respective peak power has been reached.
Display of peak power
Display range (min. value | unit | max. value)
0.0 kW 10000.0
Subcodes Information
C00143/1 Max. DC-power mot.
C00143/2 Max. DC-power reg. (+ br. chop.)
C00143/3 Max. line power reg.
Read access Write access CINH PLC STOP No transfer Scaling factor: 10
Parameter | Name:
C00144 | Time stamp of sampled max. power
Data type: UNSIGNED_32
Index: 24431
d
= 5F6F
h
From software version V2.0 onwards
Displays the elapsed-hour meter reading at which the respective peak power displayed in C00143/1...3
has been
reached.
Display of peak power
Display range (min. value | unit | max. value)
0 s 4294967295
Subcodes Information
C00144/1 Time stamp max. DC-power mot.
C00144/2 Time stamp max. DC-power reg.
C00144/3 Time stamp max. line power
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00145 | Energy out
Data type: INTEGER_32
Index: 24430
d
= 5F6E
h
From software version V2.0 onwards
Display of transmitted and regenerated energy
Display range (min. value | unit | max. value)
-2147483.647 kWh 2147483.647
Subcodes Information
C00145/1 Output energy (DC)
C00145/2 Regenerated energy (AC)
Read access Write access CINH PLC STOP No transfer Scaling factor: 1000