Chapter 6. Panel Editor 
 
6-23 
 
6) Ch 2 Communication Properties 
 
Click ‘Properties’, then the ‘Communication Properties’ window will be displayed as shown below. 
A communication parameter must be equal to the PLC to connect to. 
 
(1)  1:1 Configuration 
Specifies the communication setting when the configuration should be set as 1:1. 
 
(A) Communication Mode, HMI Station and Timeout should be set identically to the communication channel 1. 
 
(2) 1:N Configuration   
Specifies the communication setting when the configuration should be set as 1:N where one XGT Panel is set to be a 
master so to monitor several slaves. 
 
(A) Communication Mode, HMI Station and Timeout should be set identically to the 1:1 configuration.