363-206-305 System Turnup:
NTP-022
Issue 3, June 2000 Page 7 of 12
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
DO ITEMS BELOW IN ORDER LISTED . . . . FOR DETAILS, GO TO
17.
NOTE:
FiberReach shelves that are part of a subnetwork being
partitioned into multiple areas require that the NSAP
AREA
field and level 2 IS-IS routing parameters of the
ent-ulsdcc-l3 command be set. See Section 11
“Commands and Reports” in this manual for an explanation
of the command parameters. FT-2000 shelves that are part
of a subnetwork being partitioned into multiple areas require
that the L3 Area Address and Level 2 IS parameters of the
CONFIGURATION-Set-ULSDCC-L3 command be set. See
365-575-103,
FT-2000 OC-48 Lightwave System, Releases
8.1 Through 9.1, User/Service Manual
, for an explanation of
the command parameters. See 824-102-144,
Lucent
Technologies 2000
Product Family, Operations Interworking
Guide for TARP Releases
, for an explanation of the
engineering rules for subnetwork partitioning.
At the DDM-2000 shelf, use the ent-ulsdcc-l3 command to
designate the NSAPAREA field and level 2 IS-IS routing, as
required.
At the FT-2000 shelf, use the
CONFIGURATION-Set-ULSDCC-L3 command to designate the
L3 Area address and Level 2 IS parameters, as required.
DLP-514
18. Perform optical fiber connections and verification of the integrity of
the optical span being established.
19.
DLP-515
NOTE:
The rtrv-pm-line command in the following procedure
displays performance monitoring data associated with the
OC-3/OC-12 lines terminated on the system.
Perform end-to-end OC-3/OC-12 line test.
20. Repeat this procedure for all OC-3/OC-12 optical spans being
established in the FiberReach OC-3/OC-12 network. Ensure that
the last optical span connected to the FT-2000 host shelf is
connected to an Optical Interface Unit in the opposite slot as the
one in the first host FT-2000 shelf (for example, slot 1A at one
node and slot 8B at the other node).