TAP-107
: Trouble Clearing 363-206-305
Page 14 of 22 Issue 3, June 2000
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
inc. OC3 line AIS CR, MJ,
MN, or
None
The system has detected OC-3 line alarm
indication signal (AIS) on an incoming OC-3 line.
Likely cause:
Failure of an
OLIU
circuit pack at the
far end.
inc. OC3 sig degrade (BER) CR or MN The bit error ratio (BER) in the specified OC-3 line
exceeds the provisioned soft error threshold (10
–9
to 10
–5
) but below the hard error threshold of 10
–3
.
Likely cause:
Failure of the
OLIU
circuit pack at
the near end, failure of the
OLIU
circuit pack at the
far end, failure of the receive fiber, or incorrect
setting of the optical power switch on the
OLIU
circuit pack.
inc. OC3 sig failed (BER) CR or MN The bit error ratio (BER) in the specified OC-3
signal exceeds 10
–3
.
Likely cause:
Failure of the
OLIU
circuit pack at
the near end, failure of the
OLIU
circuit pack at the
far end, or failure of the receive fiber.
inc. OC12 FERF NE ACTY The system has detected the OC-12 far end
receive failure (FERF) signal in the incoming
OC-12 signal.
Likely cause:
The far end has detected an
incoming signal failure on the specified OC-12 line.
This may be caused by failure of the
OLIU
circuit
pack at the near end, the
OLIU
circuit pack at the
far end, or the transmit fiber on the specified line.
inc. OC12 LOF CR or MN The system has detected a loss-of-frame (LOF)
condition in an incoming OC-12 signal. LOF is
defined as an out-of-frame (OOF) condition (five
consecutive errored STS-1 framing patterns) that
lasts for at least 3 milliseconds.
Likely cause:
Failure of the
OLIU
circuit pack at
the near end, failure of the
OLIU
circuit pack at the
far end, or failure of the receive fiber.
inc. OC12 LOS CR or MN The system has detected loss-of-signal (LOS)
condition on the OC-12 line.
Likely cause:
Failure of the
OLIU
circuit pack at
near end, failure of the
OLIU
circuit pack at far end,
or failure of the receive fiber.
inc. OC12 line AIS CR, MJ,
MN, or
None
The system has detected OC-12 line alarm
indication signal (AIS) on an incoming OC-12 line.
Likely cause:
Failure of an
OLIU
circuit pack at the
far end.
Table B RTRV-ALM Message Descriptions (Continued)
Description
Alarm
Level Meaning