DLP-532
: Detailed Level Procedure 363-206-305
Page 4 of 4 Issue 3, June 2000
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
14.
!
DANGER:
A high discharge current is present at connector head if
TESTING
indicator is lit. Batteries must not be connected or disconnected when
TESTING
indicator is lit.
Depress test set
STOP
button. Proceed to
Step 17.
Response:
STOP
indicator on test set lights
15. After 15 minutes, the test set
COMPLETE
indicator lights.
16. Is any
REPLACE
indicator on test set lit?
If
YES
, continue with
Step 17.
If
NO
,
STOP. YOU HAVE COMPLETED THIS PROCEDURE.
17. Unplug and set aside all defective batteries.
18. Install and connect replacement batteries to battery shelf. Reconnect any
remaining good batteries to battery shelf.
19. Place batteries on high charge by depressing
HIGH RATE CHG ACTIVATE
pushbutton on
BATTERY CHARGER
and repeat from
Step 6
.