EasyManua.ls Logo

Lucent Technologies FiberReach DDM-2000 - Page 1761

Lucent Technologies FiberReach DDM-2000
1896 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
363-206-305 Detailed Level Procedure:
DLP-545
Issue 3, June 2000 Page 1 of 8
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
Perform DS3 Transmission Test
1.
NOTE:
This procedure may be used to perform DS3 transmission tests in the
mux
(toward the fiber) or
demux
(toward the DSX ) direction. When this
procedure is being used to perform end-to-end DS3 tests, it is assumed
that the complete end-to-end system has already been tested and that
only a particular DS3 channel is being tested at this time. Transmission
tests in the
mux
direction may be local or end-to-end tests (See Figure 1).
Transmission tests in the
demux
direction are local cross-connect tests
User/Service Manual, under TEST-TRMSN-T3, gives an explanation of
commands.
NOTE:
This test can be performed either with a CIT and the automated test
command test-trmsn-t3 or with a DS3 test set or M13 test set.
NOTE:
When this procedure is used to do end-to-end tests, one DDM-2000 shelf
will be referred to as the near end and the other shelf as the far end.
These designations are arbitrary; either shelf can be the near-end or the
far-end shelf.
NOTE:
Proper cross-connections must be made at each shelf to establish the
complete end-to-end path for the DS3 circuit being tested. Release 3.0
has no default cross-connections and supports only manual VT1.5
cross-connections. Release 3.1 and later has no default
cross-connections and supports only manual VT1.5 and STS-1
cross-connections. See the description of the following commands in the
"Commands and Reports" section of this User/Service Manual:
dlt-crs-vt1, dlt-crs-sts1, ent-crs-vt1, ent-crs-sts1,
rtrv-crs-vt1, rtrv-crs-sts1, set-ne, and rtrv-ne. See
Cross-Connection Provisioning
in the "Administration and Provisioning"
section of this User/Service Manual for more information on
cross-connection provisioning.
NOTE:
A CIT is required to make cross-connections for this test.
Is a CIT available?.
If YES, continue with Step 2.
If NO, proceed to Step 3.

Table of Contents

Related product manuals