EasyManua.ls Logo

M-system SC100 - Appx 5. DIGITAL DISPLAY ERROR MESSAGES

M-system SC100
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
119
SC100/200 Series Users Manual EM-6337-B Rev.15
Appx 5. DIGITAL DISPLAY ERROR MESSAGES
When more than one error has occurred at once, the most critical error is indicated.
MESSAGE DESCRIPTION PRIORITY
ERROR: EEPROM database Equivalent to GROUP 00 ITEM 21
HIGH
LOW
ERROR: PV Equivalent to GROUP 00 ITEM 22
ERROR: MV feedback Equivalent to GROUP 00 ITEM 23
ERROR: Function block Equivalent to GROUP 00 ITEM 24
ERROR: Control overload Equivalent to GROUP 00 ITEM 25
ERROR: Modbus communication Modbus communication module error (SC200/210)
ERROR: Backup module Backup error (SC110/210)
RUN CONTACT, RUN INDICATOR AND ERROR DISPLAY
FUNCTION ERROR MESSAGE
RUN CONTACT
RUN INDICATOR
REFER TO
EEPROM database destroyed ERROR: EEPROM database OFF Red
*
1
PV error ERROR: PV ON Green
*
2
MV feedback error ERROR: MV feedback ON Green
*
3
Function block error ERROR: Function block ON Amber
*
4
Control overload ERROR: Control overload ON Green
*
5
NestBus communication error ERROR: Function block OFF Amber
*
6
Comm. error between control and I/O ERROR: Function block OFF Amber
*
7
Comm. error between LCD and extension ERROR: Modbus communication ON Green
Backup module error ERROR: Backup module ON Green
Comm. error between control and LCD
-
OFF
Last display color
*
8
Control status error
-
ON RUN/STOP
*
9
RUN contact forced OFF
-
OFF Green
*
10
Backup running
-
OFF Green
*1: Function Block List Group [00], Item 21 “GROUP NN” (NN = group number)
*2: Function Block List Group [00], Item 22 “PV ABNORMAL
*3: Function Block List Group [00], Item 23 “MV ABNORMAL
*4: Function Block List Group [00], Item 24 “GROUP NN” (NN = group number)
*5: Function Block List Group [00], Item 25 “LOAD: OVER”
*6: Function Block List “Di receive terminal” and “Ai receive terminal” reception time-out (error number 21)
*7: Function Block List reception time-out to a “eld terminal” (error number 22).
*8: “Communication error” dialogue appears.
*9: Function Block List Group [00], Item 02
*10: Function Block List Group [05], Item 28 set to 1.