SC100/200 Series Users Manual EM-6337-B Rev.15
3.10. PERFORMANCE
(In percentage of max. span)
Accuracy DC input ±0.1 % ± 1 digit
Thermocouple input ±1°C ± 1 digit
±2°C ± 1 digit for B, R, S, C, PR
RTD input ±1°C ± 1 digit
Potentiometer input ±0.2 % ± 1 digit
DC output ±0.1 %
Precision resistor (REM4) ±0.1 %
Cold junction compensation ±2°C at 25 ±10°C ambient temperature
±4°C for S, R and PR
Temperature coefficient ±0.015 %/°C (±0.008%/ °F)
Line voltage effect ±0.1 % over voltage range
Calendar clock accuracy Monthly deviation 3 minutes at 25°C ambient temperature
RAM memory duration in power failure for hot start
10 minutes assured
Insulation resistance ≥ 100 MΩ with 500 V DC
Dielectric strength SC100/110 Pv1 or supply output to Pv2 or Ai1 or Ai2 or Ai3 or Ai4 to Di1 or Di2 or Di3 or
Di4 or Di5 or Pi1 or Pi2 or Pi3 or Pi4 or Pi5 to Di6 or Pi6 to Mv1 to Mv2 (or
Mv2B)*
1
or Ao1 or Ao2 to Do1 to Do2 or Do3 or Do4 or Do5 or Do6 to power
(to backup module power)*
1
to FG: 1500 V AC @1 minute
Pv2 to Ai1 or Ai2 or Ai3 or Ai4: 500 V AC @1 minute
Mv2 (or Mv2B)*
1
to Ao1 or Ao2: 500 V AC @1 minute
Do2 to Do3 to Do4 to Do5 to Do6: 500 V AC @1 minute
Pv1 to supply output: 500 V AC @1 minute
*1. SC110
SC200/210 Pv1 or supply output to Pv2 or Ai1 or Ai2 or Ai3 or Ai4 to Di1 or Di2 or Di3 or
Di4 or Di5 or Pi1 or Pi2 or Pi3 or Pi4 or Pi5 to
Di6 or
Pi6 to Mv1 to Mv2 (or
Mv2B)*
2
or Ao1 or Ao2 to Do1 to Do2 or Do3 or Do4 or Do5 or Do6 to Nest-
Bus to Modbus-RTU to power (to backup module power)*
2
to FG: 1500 V AC
@1 minute
Modbus/TCP to FG: 500 V AC @1 minute
Pv2 to Ai1 or Ai2 or Ai3 or Ai4: 500 V AC @1 minute
Mv2 (or Mv2B)*
2
to Ao1 or Ao2: 500 V AC @1 minute
Do2 to Do3 to Do4 to Do5 to Do6: 500 V AC @1 minute
Pv1 to supply output: 500 V AC @1 minute
*2. SC210
3.11. STANDARDS & APPROVALS
EU conformity EMC Directive EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive EN 61010-1
Measurement Category II (contact output)
Installation Category II (power)
Pollution degree 2
Input or output to contact output – Basic insulation (300 V)
Input or output to Power – Reinforced insulation (300 V)
RoHS Directive EN 50581
Protection against access to the terminal blocks
Finger protection (VDE 0660-514)