78
SC100/200 Series Users Manual EM-6337-B Rev.15
6.3.5.5. SETTING EXAMPLES
■ Parameters with fractions
• Setting Ao 1 parameter (ITEM 11) for ‘8-point Parameter Generator’ block (Model No. 86).
• 0.0 kg : 0.00 %, 20.0 kg : 100.00 %
Function Block List
GROUP [30]
ITEM MDFY DATA INPUT DISPLAY (e.g.) CONTENTS
◆★11
▲
±115.00% 21: NNN.NN Ao 1 Parameter
Parameter Setting
SETTING ITEM DATA INPUT
Setting Enable
Parameter CTE A1
GROUP 30
ITEM 11
Range Hi limit 200
Range Lo limit 0
Decimal place 1
Engineering unit kg
DATA Hi limit 10000
DATA Lo limit 0
DATA decimal place 2
■ Parameters in 0/1 (contact status) format
• Setting S1 internal switch (ITEM 11) for ‘Internal Switch’ block (Model No. 93).
Function Block List
GROUP [32]
ITEM MDFY DATA INPUT DISPLAY (e.g.) CONTENTS
◆★11
▲
0, 1 01: N S1 Internal switch
Parameter Setting
SETTING ITEM DATA INPUT
Setting Enable
Parameter ISW S1
GROUP 32
ITEM 11
Range Hi limit 1
Range Lo limit 0
Decimal place 0
Engineering unit 1=ON
DATA Hi limit 1
DATA Lo limit 0
DATA decimal place 0
In the above example, DATA engineering unit eld is used for a note.