61
SC100/200 Series Users Manual EM-6337-B Rev.15
6.3.1.31. START MODE
Choose hot start or cold start at the startup. With hot start setting, the module starts from the status at the moment of shut-
down. With cold start setting, it initializes all parameters before starting.
Refer to Appx 1. COLD START PARAMETERS.
6.3.1.32. NESTBUS
SC200/210
Set NestBus Card No. of the SC2x0. The Controller automatically restarts when the Card No. is changed.
6.3.1.33. MODBUS-RTU
SC200/210
Modbus-RTU setting is available for Model: SC2x0-x1-x. Restart the Controller to apply a new setting.
• Node No.
• Transfer rate
• Data bit: Fixed at 8. For reference purpose only.
• Parity: Specify the parity bit. Stop bit is set to ‘2’ with the parity set to ‘None, set to ‘1’ with ‘Even or ‘Odd’ setting.
Refer to Appx 4. MODBUS FUNCTIONS for supported functions and register assignments.
6.3.1.34. MODBUS/TCP
SC200/210
Modbus/TCP setting is available for Model: SC2x0-x2-x. Restart the Controller to apply a new setting.
• IP address
• Subnet mask
• Port No.: Fixed at 502. For reference purpose only.
• Linger time: Communication is severed when no activity is detected for the time period.
• Mac address: No setting
Refer to Appx 4. MODBUS FUNCTIONS for supported functions and register assignments.
Note
(1) IP address, Subnet mark: Set 0 or a space for higher digits when only one or two among three digits are set (e.g. 12
= ‘ 12’ or ‘012’)
(2) Default gateway: The Controller responds only to its masters queries (commands), which contains the master’s ad-
dress, therefore no default gateway setting is needed.
6.3.1.35. INITIALIZE
Initialize display setting to the factory default. Applicable parameters are indicated with X at the rightmost column of the table
in Section 6.3.1.3. CONFIGURATION PARAMETERS.
6.3.1.36. CALIBRATE TOUCH PANEL
Fine calibration for the touch panel. The screen is calibrated at the factory but may need ne re-adjustment after an extended
time period when touched point and target point reacting to the touch are misaligned.
6.3.1.37. LED TEST
SC110/210
The front LEDs for MV setting value monitor during the backup mode are turned on for testing.
6.3.1.38. LANGUAGE
Choose the display language. The language setting is not changed when the initialization (Refer to: 6.3.1.35. INITIALIZE) is
performed.
6.3.1.39. VERSION
The Controller functions are divided by blocks and shared by multiple CPU. Firmware version No. of each CPU are indicated.