IMPULSE
®
•G+ & VG+ Series 4 Technical Manual
November 2020
Page 76
B03-15 Ref Source 2 Determines what the VFD will use for
Frequency Reference. Enabled by
H01-0x = 1F.
0–4 0
0 Operator Keypad
1 Terminals Terminals or Analog Input
• S4IF Interface Board
• S4I Digital Input Option Card
• S4IO Digital Input/Output Option Card
• DI-A3 Digital Input Option Card (not used
for B03-02)
2 Serial Com Serial communication
• RS485/422 Serial Communications (R+,
R-, S+, S-)
3 Option PCB Industrial Communication Option card (Port
CN5-A)
• EtherNet/IP
• Modbus TCP/IP
•PROFINET
• PROFIBUS-DP
4 Pulse Input Pulse input via Terminal RP (H06-01)
B03-16 Run Source 2 Determines what the VFD will use for Run
Reference. Enabled by H01-0x = 1F.
0–3 0
0 Operator Keypad
1 Terminals Terminals
• S4IF Interface Board
• S4I Digital Input Option Card
• S4IO Digital Input/Output Option Card
• DI-A3 Digital Input Option Card (not used
for B03-02)
2 Serial Com Serial communication
• RS485/422 Serial Communications (R+,
R-, S+, S-)
3 Option PCB Industrial Communication Option card (Port
CN5-A)
• EtherNet/IP
• Modbus TCP/IP
•PROFINET
• PROFIBUS-DP
B03-21 PG Start Sel Allows the VFD to start when the Frequency
Reference is between D01-01 and E01-09.
0, 1 0
0 RejectRunCmd
1 AcceptRunCmd
Parameter Display Function Range Default