5.5.5 Profibus-DP (SI-P3) Option Card Setup
Settings for the Profibus-DP communication option card SI-P3.
Table 5-68: SI-P3 Parameter Settings
Parameter Display Function Range Default
F06-01 Comm Bus Flt Sel Stopping method at communication error. 0–4 1
0 Decel to Stop
1 Coast to Stop
2 Fast-Stop
3 Use B3-03 Method
4 Alarm Only
F06-02 EF0 Detection Option External Fault 0, 1 0
0 Always Detected
1 Only During Run
F06-03 EF0 Fault Action Option External Fault 0–4 1
0 Decel to Stop
1 Coast to Stop
2 Fast-Stop
3 Use B3-03 Method
4 Alarm Only
F06-04 BUS Err Det Time Set the maximum time the VFD should wait
for a communication error to occur (bUS).
0.0–5.0 sec 2.0
F06-06 Torq Ref/Lmt Sel Torque Reference Limit Selection (FLV only) 0, 1 0
0 Disabled
1 Enabled
F06-07 Fref PrioritySel Selects how multi-step speed inputs are
treated when the NetRef command is set.
0, 1 0
0 Net/Com REF Multi-step reference disabled
1 MultiStep Speed Multi-step reference enabled
F06-08 Com Prm Init Sel Determines whether communication-related
parameters (F06-xx and F07-xx) are reset
when the VFD is initialized using A01-05
0, 1 0
0 Init Com Prms Communication-related parameters (F06-xx
and F07-xx) are not reset when the VFD is
initialized using A01-05.
1 No Init Com Prms Reset all communication-related parameters
(F06-xx and F07-xx) when the VFD is
initialized using A01-05.
F06-30 PB Node Address Sets the node address if the Profibus-DP
option card is installed
0–125 0