IMPULSE
®
•G+ & VG+ Series 4 Technical Manual
November 2020
Page 71
5.1.3 Run/Reference Source
B03-01 and B03-02 determine the source from where the frequency reference and RUN command are generated.
Table 5-4: Sequence/Reference Source Parameter Settings
* Initial value is determined by X-Press Programming (Table 4-6, 4-7, or 4-8 on pages 4-12, 4-13, and 4-14).
Parameter Display Function Range Default
B03-01 Ref Source 1 Source from where the frequency reference is
generated.
0-4 1*
0 Operator Keypad
1 Terminals Terminals or Analog Input
• S4IF Interface Board
• S4I Digital Input Option Card
• S4IO Digital Input/Output Option Card
• DI-A3 Digital Input Option Card (not used
for B03-02)
2 Serial Com Serial communication
• RS485/422 Serial Communications (R+,
R-, S+, S-)
3 Option PCB Industrial Communication Option card (Port
CN5-A)
• EtherNet/IP
• Modbus TCP/IP
•PROFINET
• PROFIBUS-DP
4 Pulse Input Pulse input via Terminal RP (H06-01)
B03-02 Run Source 1 Source from where the RUN command is
generated.
0-3 1*
0 Operator Keypad
1 Terminals Terminals
• S4IF Interface Board
• S4I Digital Input Option Card
• S4IO Digital Input/Output Option Card
• DI-A3 Digital Input Option Card (not used
for B03-02)
2 Serial Com Serial communication
• RS485/422 Serial Communications (R+,
R-, S+, S-)
3 Option PCB Industrial Communication Option card (Port
CN5-A)
• EtherNet/IP
• Modbus TCP/IP
•PROFINET
• PROFIBUS-DP