5.3.6 Dwell
The Dwell function is used to temporarily hold the output frequency at a set reference for a set time. Enable by
setting H01-01 – 08 to 65.
Table 5-50: Dwell Function Parameter Settings
Figure 5-22: Dwell Function
Parameter Display Function Range Default
D08-01 Dwell Ref @ Start Sets Dwell frequency reference at start. 0.0–150.0 Hz 0.0
D08-02 Dwell Time @ Start Sets the time duration for the Dwell function at
start.
0.0–10.0 sec 0.0
D08-03 Dwell Ref @ Stop Sets Dwell frequency Reference at stop. 0.0–150.0 Hz 0.0
D08-04 Dwell Time @ Stop Sets the time duration for the Dwell function at
stop.
0.0–10.0 sec 0.0