EasyManua.ls Logo

Magnetek IMPULSE G+ 4 Series - 5.3 Tuning

Magnetek IMPULSE G+ 4 Series
256 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IMPULSE
®
•G+ & VG+ Series 4 Technical Manual
November 2020
Page 118
5.3 Tuning
D01 DC Injection Braking
D02 Motor Slip Compensation
D03 Torque Compensation
D04 Automatic Speed Regulator (ASR) Tuning
D05 Torque Control
D08 Dwell
D09 S-Curve Acceleration/Deceleration
D10 Carrier Frequency
D11 Hunting Prevention
5.3.1 DC Injection
With decel to stop enabled (B03-03=0), upon removal of the run command, the IMPULSE
®
•G+ and VG+ Series 4
VFD controls motor deceleration according to the Decel Time setting (B05-02), until output frequency reaches the
DC Injection Braking Start Frequency (D01-01 setting). Then the IMPULSE
®
•G+ and VG+ Series 4 frequency
output is turned off and DC injection current is applied to the motor. The effective DC injection time and current
should be set to provide adequate stopping without excessive motor heating. The DC injection voltage is
determined by the DC injection braking current and motor impedance.
Table 5-44: DC Injection Parameter Settings
* Not available in the Flux Vector control method (A01-02 = 3).
Figure 5-17: DC Braking Sequence
Parameter Display Function Range Default
D01-01 DCInj Start Freq DC Injection Braking Frequency Start 0.0–10.0 Hz 0.5
D01-02* DCInj Current Sets the DC Injection Braking current as a
percentage of the VFD rated current.
0–100% 50
D01-03 DCInj Time@Start DC Injection Braking Time 0.00–10.00 sec 0.00
D01-04 DCInj Time@Stop DC Injection Braking Time at Stop 0.00–10.00 sec 0.05

Table of Contents

Other manuals for Magnetek IMPULSE G+ 4 Series

Related product manuals