Page 147
5.6 Terminal Parameters
• H01 Digital Inputs
• H02 Digital Outputs
• H03 Analog Inputs
• H04 Analog Outputs
• H05 Serial Communication Setup
• H06 Pulse Input/Output
5.6.1 Digital Inputs
The IMPULSE
®
•G+ and VG+ Series 4 has eight multi-function digital inputs for the setup of numerous functions.
The following table lists the function selections for the multi-function digital inputs (terminals S1 to S8) and
indicates the control methods during which each function can be enabled. An OPE03 error will occur if a function is
programmed in more than one terminal at the same time.
Table 5-70: Digital Inputs Parameter Settings
* Initial value is determined by X-Press Programming (Table 4-6 on page 59, Table 4-7 on page 60 or Table 4-8 on page 61).
Parameter Display Function Range Default
H01-01 Term S1 Select Selects the multi-function inputs.
See Table 5-71 on page 148.
0–81 80
(FWD)
H01-02 Term S2 Select See Table 5-71 on page 148. 0–81 81
(REV)
H01-03 Term S3 Select See Table 5-71 on page 148. 0–81 *
H01-04 Term S4 Select See Table 5-71 on page 148. 0–81 *
H01-05 Term S5 Select See Table 5-71 on page 148. 0–81 *
H01-06 Term S6 Select See Table 5-71 on page 148. 0–81 *
H01-07 Term S7 Select See Table 5-71 on page 148. 0–81 *
H01-08 Term S8 Select See Table 5-71 on page 148. 0–81 *
H01-14 Alt Ref Override Alternate Frequency Reference Override.
When enabled, and an input of H01-xx = 1F is
true, will switch between Frequency
Reference Source 2 (B03-15) and the
terminals (B01-xx).
0, 1 0
0 Disabled
1 Enabled