5.1.11 Run Select
If the run reference/speed reference is switched between serial mode and VFD terminal mode, B03-07 determines
action after the switch.
Table 5-9: Run Select Parameter Settings
Parameter Display Function Range Default
B03-07 LO/RE RUN Sel Determines action after switching Run/Speed
reference source.
0, 1 0
0 Cycle Extrn RUN If the run command is present at the time
when the Run/Speed reference source is
switched, it requires the run command to be
removed and reapplied from the new source
to resume the normal operation.
1 Accept Extrn RUN If the run command is present the time when
the Run/Speed reference source is switched,
it does not require the run command from the
new source to be removed. The normal
operation will continue.
B03-08 RUN CMD at PRG Allows the Run Method to be changed via the
Local/Remote key while running.
0–2 0
0 Run
Disabled@PRG
1 Run
Enabled@PRG
2 PRG Only @ Stop
B03-10 AllowRun@PowerUp Determines how the VFD will start if a run
command is active when the VFD is powered
up.
0, 1 0
0 Cycle Ext Run Disregarded. A new Run command must be
issued after power up.
1 Accept Ext Run Allowed. Motor will start immediately after
power up if a Run command is already
enabled.