EasyManua.ls Logo

Micom P634 - Page 189

Micom P634
840 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I
d
I
ref
=
I
diff >
I
ref
Characteristics equation for the range 0.5I
diff >
< I
R
I
R,m
2
:
I
d
I
ref
= m
1
I
R
I
ref
+
I
diff >
I
ref
(
1 0.5 m
1
)
Characteristics equation for the range I
R,m
2
< I
R
:
I
d
I
ref
= m
2
I
R
I
ref
+
I
diff >
I
ref
(
1 0.5 m
1
)
+
I
R,m
2
I
ref
(
m
1
m
2
)
I
ref
: reference current
m
1
: gradient of the characteristic in range 0.5I
diff >
< I
R
I
R,m
2
m
2
: gradient of characteristic in range I
R,m
2
< I
R
2
4
6
8
2 4 6 8
I
IIIII
64Z9003A
Tripping area
m1 = 0.3
m2 = 0.7
= 0.2
Id>
Iref
IR
Iref
Id
Iref
IR,m2
Iref
= 4.0
Blocking area
Fault current characteristic
for single-side feed
Id>
Iref
* 0.9
Hysteresis active
Fig. 3-91: Tripping characteristic of differential protection
Differential protection can optionally be set to trip with a definite time delay
(setting 010 162 DIFF: Op.del.,trip sig.PSx), used for selectivity between
overlapping differential protection zones. For such applications, also the
hysteresis of the tripping characteristic should be enabled (setting 072 006
DIFF: Hyst. effective PSx = Yes), to avoid chattering operation for faults/test
conditions close to the trip characteristic. Upon differential starting
DIFF: Starting, the hysteresis gets activated, i.e. the basic threshold Idiff> (or
Idiff>(CTS) respectively) is reduced to 90% of the set value. All other
characteristic settings are unchanged. Thus the characteristic is "vertically"
moved towards lower differential current values.
3 Operation
P634
P634/EN M/R-42-A // P634311653 3-133

Table of Contents

Related product manuals