2.2 General Data
2.2.1 General Device Data
Design
Surface-mounted case suitable for wall installation, or
Flush-mounted case for 19 cabinets and for control panels.
Installation Position
Vertical ± 30°.
Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 529.
IP 52 for the front panel.
Flush-mounted case:
o
IP 50 for the case (excluding the rear connection area)
o
IP 20 for the rear connection area, pin-terminal connection
o
IP 10 for the rear connection area, ring-terminal connection
Surface-mounted case:
o
IP 50 for the case
o
IP 50 for the fully enclosed connection area with the supplied rubber
grommets fitted
Weight
40 TE case: Approx. 7 kg
84 TE case: Approx. 11 kg
Dimensions and Connections
See dimensional drawings (Section 4.2, (p. 4-4)), and the location and
terminal connection diagrams (Section 5.7, (p. 5-22)).
Terminals
PC interface (X6)
EIA RS232 (DIN 41652) connector, type D-Sub, 9-pin
Communication interfaces COMM1, COMM2
Fiber (X7, X8)
o
F-SMA optical fiber connection per IEC 608742 (for plastic fibers), or
o
optical fiber connection BFOC-ST
®
connector 2.5 per IEC 60874101 (for
glass fibers).
(ST
®
is a registered trademark of AT&T Lightguide Cable Connectors.)
Wire leads (X9, X10)
o
M2 threaded terminal ends for wire cross-sections up to 1.5 mm² (US:
AWG16).
IRIG-B Interface (X11)
o
BNC plug
P634
2 Technical Data
2-2 P634/EN M/R-42-A // P634311653